1. Background
Distributed PV plants are mostly built on building rooftops and factory roofs. This makes later O&M inconvenient. PV data acquisition technology remotely collects data from auxiliary equipment and enables unattended operation. It reduces O&M costs, improves generation efficiency and delivers considerable economic value.

PV Plant Data Acquisition Solution
The inverter is the core component of a PV plant. It converts the DC power generated by PV modules into AC power for local loads or the grid (self-consumption or grid connection), and provides the associated protection functions. Its performance directly affects the efficiency and stability of the entire PV generation system, so remote data acquisition of inverters is highly valuable.
The inverter data that can be collected falls into two main categories: 1. PV module electrical parameters such as voltage, current, power, power factor and energy generation; 2. Fault and alarm information, including module and inverter faults and generation anomalies. Analyzing fault alarms and generation parameters improves efficiency and reduces losses.
2. Solution Implementation
2.1 Requirements Analysis: The following describes in detail the data acquisition for the inverters at a PV plant.

Inverter Example
Characteristics: the inverters are concentrated in a small area and of a single model, so an RS-485 bus is suitable. Compared with the high-cost option of giving each inverter its own acquisition stick, this offers two advantages: 1. Interface-based acquisition lets the user keep control of the data, unlike the manufacturer’s acquisition sticks that are locked to a specific platform. 2. Lower cost: fewer hardware acquisition products, and compared with 4G wireless acquisition the corresponding data-traffic charges are also saved.
2.2 Acquisition Solution

Inverter Data Acquisition Solution
Implementation: 1. Connect the inverters to the Daq IoT gateway over an RS-485 line;
-
Configuration software pushes settings remotely to the cloud platform, which forwards them to the gateway over the MQTT protocol;
-
Collect inverter data over the Modbus RTU protocol and upload it to the cloud platform;
Huawei Inverter Modbus Configuration Point List (contact sales staff for a copy); confirm compatibility against the specific device model (partial example below).
| Device Name (DevName) | Tag Name (TagName) | Thing Model Identifier (Point Description) | Function Code | Read/Write Attribute | Coefficient K | Offset B | Variable Unit | Point Group | Register Address | Data Type | High/Low Byte Order |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Huawei PV Inverter | Ub | Ub | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32278 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Uc | Uc | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32279 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Ia | Ia | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32280 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Ib | Ib | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32281 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Ic | Ic | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32282 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | COS | Power Factor | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.001 | 0.0 | 0 | 32284 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Ef | Inverter Efficiency | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.01 | 0.0 | 0 | 32285 | 16-bit unsigned | 12 | |
| Huawei PV Inverter | Temp | Internal Temperature | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.1 | 0.0 | 0 | 32286 | 16-bit signed | 12 | |
| Huawei PV Inverter | P | Active Power | 0x03, 0x06 commands (read/write holding registers) | Read-only | 1.0 | 0.0 | 0 | 32290 | 32-bit signed | 12 | |
| Huawei PV Inverter | Q | Reactive Power | 0x03, 0x06 commands (read/write holding registers) | Read-only | 1.0 | 0.0 | 0 | 32292 | 32-bit signed | 12 | |
| Huawei PV Inverter | Pdc | Total DC Power | 0x03, 0x06 commands (read/write holding registers) | Read-only | 1.0 | 0.0 | 0 | 32294 | 32-bit signed | 12 | |
| Huawei PV Inverter | DE | Daily Energy Generation | 0x03, 0x06 commands (read/write holding registers) | Read-only | 0.01 | 0.0 | 0 | 32300 | 32-bit unsigned | 12 |
(The full table is longer; only the first 12 rows are shown here.)
Compatible Huawei PV inverter models:
SUN2000-42KTL, SUN2000-36KTL, SUN2000-33KTL-A, SUN2000-50KTL-C1, SUN2000-50KTL-M0, SUN2000-50KTL, SUN2000-60KTL-M0, SUN2000-60KTL, SUN2000-55KTL, SUN2000-60KTL-HV-D1

Wiring Example